Are Fire Sprinklers
Required Everywhere?
As the debate continues for
the use and implementation of fire sprinkler systems, there are some things
that home inspectors should know. Currently only the entire state of California require
sprinkler systems in all single family and larger residences. Many individual
municipalities are requiring residential sprinkler systems. Multiple units and
commercial buildings already have the requirement in place in most areas. Some
materials approved are steel pipe, black iron, PEX, copper, and CPVC (orange in
color). I see mostly orange CPVC. Probably due to cost and ease of
installation, however there are some issues associated with its use. Some
products may degrade CPVC and must be considered before employing it. Some types
of caulk, fire stopping products, mold / antimicrobial products, certain types
of pipe tape, certain thread sealants, some leak detector fluids, coated pipe
hangers, and one type of waterproofing. Any of these products may degrade CPVC
and should not come in contact with it. Fire sprinkler pipes need to be secured
to ensure they do not uplift under pressure. Where are the areas that fire
sprinklers are not required according to NFPA 13 – 903.3.1.1.1 & 2;
903.3.1.1.1 Exempt
Locations
Automatic sprinklers shall not be required in the
following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible
particles of combustion. Sprinklers shall not be omitted from a room merely
because it is damp, of fire-resistance-rated construction or contains
electrical equipment.
1.
A room where the application of water, or flame and water, constitutes
a serious life or fire hazard.
2.
A room or space where sprinklers are considered undesirable
because of the nature of the contents, where approved by the
fire code official.
3.
Generator and transformer rooms separated from the remainder of
the building by wallsand floor/ceiling or roof/ceiling assemblies having
a fire-resistance rating of not less than 2 hours.
4.
Rooms or areas that are of noncombustible construction with
wholly noncombustible contents.
5.
Fire service access elevator machine rooms and machinery spaces.
6.
Machine rooms, machinery spaces, control rooms and control
spaces associated with occupant evacuation elevators designed in accordance
with Section 3008.
903.3.1.1.2 Bathrooms
In Group R occupancies, other than Group R-4occupancies, sprinklers shall not be required in bathrooms
that do not exceed 55 square feet (5 m2) in area and are located
within individual dwelling units or sleeping units, provided that walls and ceilings, including the wallsand ceilings behind a shower enclosure or tub, are of
noncombustible or limited-combustible materials with a 15-minute thermal
barrier rating.