Friday, February 15, 2019
ARC Fault Circuit Protection and Home Inspections – PART 1- Service Panel inspection
ARC Fault Circuit Protection and Home Inspections – PART 1- Service Panel inspection
Section
201.12 of the 2014 National Electric Code (NEC) now requires arc fault (AFCI)
protection in all areas that do not currently require Ground Fault Circuit
Interrupters (GFCI’s). Arc fault’s occur basically when current travels through
air. This happens because of loose or incomplete connections, or possibly a
screw or nail has penetrated or come in contact with a conductor. Think of a
spark plug as one example of an electrical arc. These “arcs” can be several
thousands degrees strong, while still drawing less current than is necessary to
interrupt the circuit, or “trip” the breaker thus creating a fire hazard. So
how should these be inspected? We will
look at the only six accepted installation methods for arc fault (AFCI)
protection next month. This month we will focus on the service panel and the difference
between a Combination AFCI, and a Branch/Feeder type AFCI circuit breaker
MORE……
Differences between a Combination and Branch / Feeder AFCI Breaker
It
is extremely important to note that a “combination” AFCI circuit breaker does not mean
that it provides both AFCI and GFCI protection. Both Branch Feeder and
Combination AFCI’s provide conventional thermal and magnetic overcurrent
protection. Both provide high current or parallel arcing fault detection and
fire protection for branch circuit wiring and connected cords. The Combination
AFCI has the added benefit of enhanced detection of persistent low current or
series arcing faults which mitigate fire hazards in extension cords connected
to receptacles. The circuit breaker will also be labeled – “Combination Type”
or “Branch/Feeder” AFCI.
Inspection in the main service panel –
Looking
at the pictures at the beginning of the article, you can see that there is a
white wire attached to the AFCI circuit breaker. This wire should be connected
to the neutral bus in the electric service panel. The hot and neutral branch
circuit wires will both be connected to the ARCI breaker. The installation is
similar to that of a GFCI circuit breaker. Pressing the test button on the
circuit breaker itself or using a AFCI tester in the branch circuit are the
best ways to test it. The inspector should make a mental note if the breaker is
a combination or branch feeder because they are used for AFCI protection in
different combinations. If the wrong type of AFCI breaker is used the circuit
may not be properly protected. This will also give us a clue as to whom may
have installed the AFCI. For instance if a Combination type AFCI is installed
for a branch circuit in the service panel, then no other additional
requirements are necessary. However if a Branch/Feeder AFCI breaker is
installed for a branch circuit, then an additional AFCI receptacle outlet is
required to be installed at the first outlet box. Double pole Combination AFCI
circuit breakers are installed the same as outlined above. They should be used
for 240 volt circuits and multi-branch circuit wiring. Some manufactures have
light indicators on the AFCI circuit breakers that will indicate why and
possibly when the AFCI was tripped. For instance if the trip was a result of an
arcing fault, an arcing fault to ground, or if it tripped as a result of an
overcurrent condition. Any light or trip indicators should be noted.
Subscribe to:
Post Comments (Atom)

No comments:
Post a Comment