Electric
Receptacle Placement
Of course
you put a tester in the receptacles during the inspection. We are going to look
at receptacles a little differently. The
most common types of branch circuits are; General Purpose (15 or 20 amp,
lighting, and general purpose receptacles), Small Appliance Circuits (usually
20 amp, found in kitchens and other areas where small appliances are located),
Individual Circuits (Supply a single appliance or receptacle, normally 20 amps
and more). 240 Volt circuits should be on their own circuit.
Common
duplex receptacles have two outlets and
are connected by a metal tab. If this tab is removed, each outlet can be
wired to a separate circuit. A 20 amp receptacle has a horizontal slot
connected to the vertical slot on the neutral side. I often wonder why someone
would run #12 AWG and install a 15 amp receptacle. When conducting a home
inspection, receptacle placement is something we should be looking for. Not for
code compliance, or home inspection standards, but for our clients convenience.
If there is one receptacle in a room, we would recommend adding additional
receptacles, a pull chain in the center of a room would warrant a wall switch.
Receptacle placement may also indicate if a qualified electrician wired the house
or not. For our clients convenience, and
in my opinion, a good quality inspection, we should look for the following:
•
A
receptacle outlet must be installed so that no point along the wall space will
be more than 6 feet horizontally from another receptacle. This is to ensure
that a 6 foot cord will reach the receptacle, so an extension is not needed.
•
Wall
sections, fixed exterior glass panels, counters and railings that are at least
2 feet long and uninterrupted along the floor by doors, openings, or
fireplaces. Sliding portions of glass doors on exterior walls are not
considered wall space.
•
Receptacles
in rooms should be located 12-16 inches from the floor (switches should be
46-48 inches from the floor).
•
Two
or more small appliance circuits of at least 20 amperes are required in all
kitchens. These circuits must be dedicated and therefore not connected to any
other circuit.
•
In
kitchens, a receptacle must be installed at each wall counter space 12 inches
or wider. Receptacles must be installed no further than 24 inches apart
measured horizontally, this means the first receptacle must be located not more
than 24 inches from the edge of the counter space, and the next receptacle can
be no more than 48 inches from the first one.
Lighting
in closets are not required, but many homes do have lights in closets. We
should be looking for the following;
•
Exposed
light bulbs are not acceptable in closets
•
Totally
enclosed incandescent fixtures must be a minimum distance of 12 inches from the
storage space and surface mounted fluorescent fixtures must be a minimum
distance of 6 inches from the storage space.
•
Completely
enclosed recessed fluorescent fixtures must be at least 6 inches from the
storage area
No comments:
Post a Comment